Home arrow . arrow pH Transmitter arrow pH Transmitter Unit
Info: Your browser does not accept cookies. If you want to put products into your cart and purchase them you need to enable cookies.

PDF



pH Transmitter Unit

Code: GB-MP/

Price:  Call for Pricing


Availability

Usually ships in:

1-4w.gif


Danntech's new DIN Rail Mounting pH Transmitter is a low cost alternative for applications where local display is not required. Any pH electrode can be used with a variety of temperature compensation inputs. Based upon 24 bit analogue to digital conversion, this transmitter provides excellent accuracy and galvanic isolation in a compact package. The transmitter is configured using a PC and a configuration program to do the zero and span calibration as well as setting up the operation of the relay outputs and LEDs. The analogue output can be scaled to any range with filtering and inversion options.
The two relay outputs can be configured as alarms with selectable operating sense and hysteresis or as control outputs.
A simple ASCII protocol is used to connect using RS485 so that multiple units can be connected to a controlling system.
It is possible to use the transmitter in a passive mode, where it operates like a Remote Terminal Unit (RTU) with a 24 bit pH input, a 24 bit temperature input, a 12 bit analogue output, two relay outputs and two LED outputs each individually accessible and controllable.
The unit is 24 VDC powered and three way isolation up to 1000 VDC ensures trouble-free operation in process control environments where ground loops and noise may be prevalent. Economical, DIN rail mounting, pH or ORP (Redox) transmitter for process control applications where local display of the pH is not required. Basic 24 bit measurement accuracy with temperature compensation. pH and Redox calibration using front panel controls with detailed configuration using PC and configuration software.
Specifications:
  • pH input from any electrode 0 to 14 pH.
  • ORP/Redox potential ±1000 mV.
  • 24 bit input resolution.
  • Input impedance >10 GΩ.
  • Input zero and span adjustment.
  • Analogue output - 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 0 to 10 V, ±5 V and ±10 V (factory configured).
  • User friendly software calibration, output scaling, relay and LED operation, configurable zero, full-scale adjustment.
  • Maximum output load resistance 470 Ω for current outputs.
  • Minimum output load resistance 1 kΩ for voltage outputs.
  • 12 bit output resolution.
  • Linearity better than 0.5% of the range.
  • Output response - set by filter selection 0.1 to 60 seconds.
  • LEDs to indicate power in, a fault condition and communications activity.
  • Two signal relay outputs (24 V at 1 A) with configurable operating sense - normally open or normally closed.
  • RS232 using the Configuration Cable.
  • Isolated RS485 communications on terminals 15 and 16 as well as via the DIN rail plug-in connector.
  • Rear plug-in DIN rail bus connection for power and RS485 communications.
  • RS485 baud rates 9 600 or 19 200 bits/sec.
  • Galvanic isolation between auxiliary supply, input, output and RS485 communications > 1 000 VDC.
  • 24 VDC (-5%, +10%) auxiliary power supply at approximately 100 mA.
  • Operating temperature -10°C to 60°C, storage temperature -20°C to 70°C.
  • DIN rail mounting with plug-in screw terminal connections.
  • Dimensions - 22.5 x 118 x 113 mm (width x length top to bottom x height off DIN rail).