DC Power Supply 24V 2.5A 115..230VAC
Code: GB-PS/24-2.5/AB
Price: Call for Pricing
View Datasheet (pdf) (110,43 KB)
Availability
Usually ships in:
97-265 VAC input. Safety to VDE 0805 / EN 60950. High efficiency. Radio interference suppressed to VDE 0875 T11 / EN 55011. Interference to EN 50082-2. Protected against continuous short circuit and continuous idle. Connection via screw plug-in connectors. Compact, low weight housing. "On" indicator (LED)
Input:
Input Voltage
97-265 VAC,47-63 Hz
Nominal Input Current
0.6 A at 230 VAC
Switch-on Surge
Current Fuse
30 A 5 x 20 mm,
T2.5 A/250 V Internal
Power Factor cos phi
0.42 capacitive
Safety:
Tested in accordance with VDE 0805, EN 60950
Protection Class
Class 1
Degree Of Protection
IP 20
Leakage Current
< 0.75 mA (47 - 63 Hz)
EMV CE Certified
EN50081-1/-2, EN50082-1/-2
Radio interference
EN55011/EN55022 Class B
Static Discharge
ESD IEC 1000-4-2 8 kV
contact discharge,
15 kV air discharge
Electromagnetic Fields
IEC 801-3 10 V/m
Burst
IEC 801-4 4 kV input
2 kV output/capacitor coupled
Surge
IEC 801-5 4 kV
asymmetric: L ,N --> PE
4 kV symmetric: L --> N
Output:
Output Voltage
24 V ±1%
Adjustment Range
22.5 - 27.5 V
Output Direct Current
0 - 2.5 A
Ripple
< 50 mV
Current Limit, typical
3 A
Efficiency, typical
86%/font>
Regulation:
Line Regulation
0.2 % with Vin = 97 - 265 VAC
Load Regulation
< 0.5 % with Iout = 0 A - 2.5 A
Dynamics
< 2 ms with load change from
10% to 90%
Peak overshoot < 2%
Operational Data:
Temperature Range
0 to +70°C with free convection
Power Derating
2.5%/K from +60°C
Storage Temperature
-25 to +85°C
Protection and Monitoring:
Internal fuse
5 x 20 mm, T 2.5 A/250 V
Current Limitation
Protected against continuous
short circuit
Hold up Time
> 80 ms with Vin = 230 VAC
> 15 ms with Vin = 115 VAC
Mechanical Data:
Dimensions
108 x 105 x 65 mm (L x W x H)
Weight
0.6 kg
Installation
DIN Rail Mounting
Mounting Position
Wall mounted
Input terminals on top
Output terminals underneath
Last Updated: