 View More Images (4) |
Quad Isolating Signal Converter 24/12 VDC
|
Code: GB-QSP/0002/C
Price: Call for Pricing
|
View Datasheet (pdf) (301,45 KB)
Availability Usually ships in:

Four separate isolated transmitters in a compact package providing a variety of “factory configured” input and output options.
Inputs can be:
Voltage: 0-50 mV, ±50 mV, up to 0-100 V or ±100 V. Standards are 0-10 V and ±10 V.
Current: 0-20 mA, 4-20 mA, 0-5 mA, 0-1 mA as well as bipolar current inputs up to ±200 mA. Standards are 0-20 mA and 4-20 mA.
Outputs can be:
Voltage: 0-10 V and ±10 V at up to 5 mA, with maximum ±12 V.
Current: 0-20 mA, 4-20 mA, 0-5 mA or 0-1 mA. Maximum 500 Ω.
Auxiliary supply can be 24 or 12 VDC.
Specifications:
-
Four analogue inputs - 0-20 mA, 4-20 mA or 0 - 10 V DC (others on request).
-
Four analogue output - 0-20 mA, 4-20 mA or 0-10 V.
Two Digital Inputs – 15 to 30 VDC at 12 mA maximum, optically isolated, polarity protected.
-
Two Digital Outputs – 30 V at 30 mA maximum, optically isolated.
-
Optional RS232 and RS485 communications.
-
±10% over and under-range on the inputs and outputs.
Input Impedance – Voltage Input: > 100 kΩ.
-
Input Impedance – Current Input: 100 Ω.
-
Input Analogue to Digital Resolution – 10 bits or approximately 0.3% of full scale input.
-
Output load >2 kΩ for voltage outputs and 500 Ω maximum for the current output.
Output Current Maximum – Voltage Output: 5 mA.
-
Output Current Maximum – Current Output: 22 mA.
-
Output Current Minimum – Current Output: 0.2 mA.
-
Output Voltage Maximum – Current Output: 12 V.
-
Output Voltage Minimum – Voltage Output: -12 V
-
Output Digital to Analogue Resolution – 12 bits or approximately 0.06% of full scale output.
-
Output zero and span software adjustable.
-
Linearity better than 0.2% of full scale.
-
Power On LED (green) flashing at approximately 1 Hz.
-
Step Response – Input to Output: 10 mSec or less.
-
Auxiliary Power Supply: 24 VDC +10%, -5% at 200 mA max. (by special request 12 VDC models can also be supplied)
-
Isolation between input, output and auxiliary power supply >1000 VAC.
-
Operating temperature -10°C to 60°C, storage temperature -20°C to 70°C.
Calibration sheet provided for each unit manufactured.
-
DIN rail mounting.
-
Screw terminal connections.
-
Weight – 275 g.
|
|
|
|
|