Input signal frequency range from 0.01 Hz to 100,000 Hz. Standard operating ranges: One pulse per hour to one pulse per second 0.001 to 10 Hz, 0.01 to 100 Hz, 0.1 to 1,000 Hz, to 10,000 Hz, 10 to 100,000 Hz.
Input types: AC - 10 V AC to 250 V AC (mains and other larger AC signals). AC – 50 mV AC to 10 V AC (impeller type flowmeters). DC offset - < 2 V to > 15 V (proximity switches, potential free contacts) DC offset - < 9 V to > 18 V DC offset – others Namur
±10% over and under-range on the input.
Output signal range 4-20 mA, 0-20 mA, 0-10 V, 0-5 V, ±10 V.
When input frequency goes below the “drop-out” frequency for the “drop-out” delay time the output goes to the “drop-out’ output value (all configurable).
Output zero and span adjustable approximately ±10% of the range
Step response approximately 10 mSec for frequency inputs above 100 Hz and at input frequency below 100 Hz.
Linearity better than 0.2% of full scale.
Input LED flashes with the input (yellow) indicating that the input is detected.
Input supply 24 VDC, 12 VDC ±10% or 22 to 30 VDC.
Isolation between input, output and DC supply >1000 VDC.
Operating temperature -10 to 65°C.
Calibration sheet provided for each unit manufactured.