GB-HS-Specifications

  • Standard input signal ranges of ±10 mV, 0-10mV, ±20 mV,
    0-20mV and many others up to ±1 000 mV.
  • High quality intrumentation amplifier front end.
  • Input impedance >3 M.
  • High speed optical isolation > 2 kV.
  • -3dB bandwidth 6 kHz for ±10 mV input, 10 kHz for ±20 mV input, 15kHz for ±40 mV input.
  • Voltage output signal ranges of 0-10V, ±10 V, 0-5 V or ±5 V.
  • Current outputs 0-20mA and 4-20 mA.
  • Output load >2 k for the voltage output.
  • Multi-turn trimpot adjustment for Output zero and span and
    Input zero and span.
  • 10% over-range capability.
  • Linearity better than 0.25% of full scale.
  • Bridge excitation supply 5.000 V to 10.000 V at maximum 30 mA, DIP switch selectable.
  • Input supply 115 or 230 VAC ±10% 50/60 Hz or 12 or 24 VDC.
  • Isolation input to output 2 500 VAC for 115/230 VAC powered units, >1000 VDC for DC powered units.
  • Operating temperature -10 to 60°C.
  • 24 hour operational burn-in.
  • Calibration sheet provided for each unit manufactured.
  • DIN rail mounting.
  • Screw terminal connections.
  • Dimensions 40 x 80 x 85 mm (W x H x D).