- Input impedance of 100 kΩ for the voltage input and 50Ω for the current input models.
- Maximum input signals of 100 V for voltage input and 15 A for the current input.
- Output load 2 kΩ for the voltage output and 500 Ω maximum for the current output.
- Step response approximately 200 ms.
- Linearity better than 0.1% of full scale.
- Auxiliary supply 24 VDC or 12 VDC ±5%.
- Isolation between input, output and auxiliary power supply 1,000 VDC.
- Operating temperature -10°C to 70°C.
- 24 hour operational burn-in.
- Calibration sheet provided for each unit manufactured.
- DIN rail mounting with dimensions 25 x 80 x 85 mm (W x H x D).