  • Input options are 0 to 10 V, 0 to 5 V, ±10 V, 0 to 20 mA, 4 to 20 mA, resistance (potentiometer).
  • Output options are 0 to 10 V, ±10V (up to 1330 mA), current output up to ± 1330 mA.
  • Selectable filtering dip switch selectable with fastest step response of 10 mS or less.
  • Requires an external DC supply of either: 9 to 18 VDC (12 VDC nominal),
    18 to 36 VDC (24 VDC nominal), 36 to 75 VDC (48 VDC nominal).
  • Supply current typically Iout + 100 mA.
  • Isolation of up to 1500 VDC or more, between input, output and the auxiliary power supply.
  • Isolation of up to 1500 VDC or more, between input, output and the auxiliary power supply.
  • Zero and span adjustment.
  • Optional RS485 communications with our simple command interface so multiple units can be used with remote control.
  • Modbus communications option in development.
  • Hydraulic valve controller option available on request with dither and ramping.
  • Heatsink temperature monitoring with automatic shutdown at 80°C and restart at 70°C.
  • Operating temperature -10°C to 60°C.
  • DIN rail mounting.
  • Plug-in screw terminal connections.