GB-VT-Specifications

  • Standard input and output signal ranges 4-20 mA and 0-10V.
  • Input ranges, from 50 mV to 100 V, 1 mA up to 10 A DC.
  • Output ranges, from 0-1 V to ±10 V (0 to 100 mV on request), up to 22 mA.
  • Bipolar input and output configurations.
  • Customised input and output ranges on request.
  • Selectable filtering options up to 60 seconds.
  • Zero and span trimpots can be locked or disabled using a DIP switch.
  • Wide or normal zero and span adjustment selection using a DIP switch.
  • Input impedance of >100 kΩ for the voltage input and 50 Ω for the current input models.
  • Maximum input signals of 100 V for voltage input and 10 A for the current input.
  • Output load >2 kS for the voltage output and 500 S maximum for the current output.
  • Step response approximately 200 ms.
  • Linearity better than 0.1% of full scale.
  • Auxiliary supply 24 VDC or 12 VDC ±5%.
  • Isolation between input, output and auxiliary power supply 1,000 VDC.
  • Operating temperature -10°C to 70°C.
  • 24 hour operational burn-in for every device.
  • Calibration sheet provided for each unit manufactured.
  • DIN rail mounting with dimensions 25 x 80 x 85 mm (W x H x D).